SECTION
11208
METERING
MANHOLES
PART
1 GENERAL
1.1 SECTION INCLUDES
A.
Metering
manholes.
1.2 RELATED SECTIONS
A.
Section
03300 - Cast-In-Place Concrete.
B.
Section
11206 - Palmer-Bowlus Flumes.
C.
Section
11207 - Parshall Flumes.
D.
Section
11286 - Slide Gates and Guides.
1.3 REFERENCES
A.
ANSI/AWWA
F101 - Contact Molded, Fiberglass-Reinforced Plastic Wash Water Troughs and
Launders; American Water Works
Association.
B.
ASTM
D 256 - Standard Test Methods for Determining the Pendulum Impact Resistance of
Notched Specimens of Plastics.
C.
ASTM
D 638 - Standard Test Method for Tensile Properties of Plastics.
D.
ASTM
D 790 - Standard Test Methods for Flexural Properties of Unreinforced and
Reinforced Plastics and Electrical Insulating Materials.
E.
ASTM
D 2583 - Test Method for Indentation Hardness of Rigid Plastics by Means of a
Barcol Impressor.
F.
ASTM
D 3753 - Standard Specification for Glass-Fiber-Reinforced Polyester Manholes.
1.4 SUBMITTALS
A.
Submit
under provisions of Section 01300.
B.
Product
Data: Test results of fiberglass
reinforced plastic laminate.
C.
Shop
Drawings: Show:
1.
Critical
dimensions, jointing and connections, fasteners and anchors.
2.
Materials
of construction.
3.
Sizes,
spacing, and locations of structural members, connections, attachments,
openings, fasteners, and loads.
D.
Manufacturer's
installation instructions.
1.5 DELIVERY, STORAGE, AND HANDLING
A.
Store
products indoors and protect from construction traffic and damage.
PART
2 PRODUCTS
2.1 MANUFACTURER
A.
Provide
products manufactured by Warminster Fiberglass Company; P.O Box 188,
Southampton PA 18966-0188; ASD. Tel.
(215) 953-1260, Fax. (215) 357-7893, www.warminsterfiberglass.com.
B.
Requests
for substitution will be considered in accordance with provisions of Section
01600.
C.
Substitutions: Not permitted.
2.2 METERING MANHOLES
A.
Fiberglass
Laminate:
1.
Tensile
strength (ASTM D 638): 14,000 psi.
2.
Flexural
strength (ASTM D 790): 25,000 psi.
3.
Flexural
modulus (ASTM D 790): 1,000,000 psi.
4.
Impact,
notched, Izod (ASTM D 256): 15
ft-lb/in.
5.
Barcol
hardness (resin-rich surface) (ASTM D 2583): 40 minimum, average.
6.
Coefficient
of thermal expansion, average (ASTM D 696): 0.000105 in/in/degree F.
7.
Test
coupons prepared in accordance with ASTM D 618.
8.
Chemical
resistance: Comply with ANSI/AWWA F101,
Type II classification.
B.
Construction: Fiberglass reinforced plastic, complying
with ASTM D 3753; factory-assembled,ready for installation except for
field-installed equipment.
1.
Interior
surface smooth and resin rich; free of pits, porosity, cracks, crazing, and dry
glass.
2.
Exterior
laminate: 1/2 inch thick, minimum,
consisting of polyester resin with 25 percent minimum glass content.
3.
Cover: 1/4 inch thick fiberglass, hinged one side,
with hasp for locking; provide soft neoprene sponge gasket for sealing.
4.
Inlet
and outlet pipes: Integrally molded to
manhole with laminates on both the interior and exterior surfaces; inlet and
outlet boots with stainless steel straps to diameter of inlet and outlet pipe.
5.
Access
ladder: Fiberglass; bolted to manhole
wall.
6.
Mounting
flange: 4 inch, integrally molded
around circumference of manhole for anchoring to concrete pad.
7.
Gasket: 1/2 inch thick neoprene sponge pad.
8.
Size: 48 inch diameter, with 51 inch diameter
cover.
9.
Size: Reduced manway, 21 inch diameter opening.
10. Size: Reduced manway, 24 inch diameter opening.
11. Size: As indicated on drawings.
12. Height: As indicated
on drawings.
C.
Flume
Assemblies: Laminate flumes into
manholes to form a totally watertight assembly.
1.
For
flumes longer than manhole diameter, cover flume with fiberglass plate of
sufficient strength laminated to make watertight seal and to withstand loads
when backfilled.
D.
Accessories:
1.
Anchor
bolts: Type 304 stainless steel.
2.
Full
open, hinged cover with locking latch.
3.
Staff
gauge graduated in 50 divisions per foot mounted inside flume.
4.
Staff
gauge graduated in inches mounted inside flume.
5.
Stilling
well, 10 inches diameter.
6.
Bubbler
tube.
7.
Tracks
for probes, molded in.
8.
Bushing
for ultrasonic transponder mounting.
9.
Bulkhead
fittings.
PART
3 EXECUTION
3.1 EXAMINATION
A.
Verify
that dimensions are correct and project conditions are suitable for
installation. Do not proceed with
installation until unsatisfactory conditions have been corrected.
3.2 INSTALLATION
A.
Install
products in accordance with manufacturer's instructions.
B.
Ensure
that products are installed plumb and true, free of warp or twist, within
tolerances specified by the manufacturer and as indicated in the contract
documents.
C.
Verify
that concrete slab is level and smooth trowelled. Level with grout if necessary.
Ensure that piping is self-supported by bedding.
D.
Handle
manhole using slings of nylon or similar fabric. Do not drop or impact.
E.
Place
sponge pad on concrete slab. Drill
holes in accordance with template for stainless steel anchor bolts.
F.
Lower
manhole onto pad and install anchor bolts.
G.
Check
level of flume in both planes, and adjust as required.
H.
Connect
piping. Do not lubricate neoprene
boots. Secure with stainless steel
clamp.
I.
Backfill
with pea gravel, 1/4 inch to 3/4 inch diameter, specified in Division 2, using
uniform lifts not exceeding 12 inches.
J.
Where
cut holes are required, seal as directed by the Engineer.
3.3 ADJUST AND CLEAN
A.
Clean
surfaces in accordance with manufacturer's instructions.
B.
Remove
trash and debris, and leave the site in a clean condition.
END OF SECTION